Final | 3/28/2005 | 3/28/2005 | 3/28/2005 | P | PASS |
Bob Reichert
|
|
|
re-insp for a19 hampton est ---brent; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie corrections made, p/s o/h exst pole with meter ok 3/28/2005 3:04:16 PM
|
DOC - Permit Finaled | 3/28/2005 | 3/28/2005 | 3/28/2005 | P | PASS |
Bob Reichert
|
|
|
Finaled by inspector at 3/28/2005 3:04:19 PM
|
Permanent Service | 3/25/2005 | 3/25/2005 | 3/25/2005 | P | FAIL |
Bob Reichert
|
|
|
###-#### - brent called contr, left corr notice, 250.53(B) electrodes shall be min 6' apart, 250...53(G) electrode shall be driven to full depth or less than 45 degrees, 110.12(A) unused openings shall be closed 3/25/2005 1:21:06 PM
|
Issue permit | | | 3/25/2005 | | DONE |
|
|
|
|
Application received | | | 3/25/2005 | | |
|
|
|
|