Final | 6/16/2005 | 6/16/2005 | 6/16/2005 | P | PASS |
Bob Reichert
|
|
|
call for access///kevin; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final
|
Permanent Service | 4/4/2005 | 4/5/2005 | 4/5/2005 | A | PASS |
Bob Reichert
|
|
|
kevin; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corrections made p/s o/h n ok 4/5/2005 7:40:02 AM
|
Permanent Service | 4/4/2005 | 4/4/2005 | 4/4/2005 | P | FAIL |
Bob Reichert
|
|
|
kevin ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie 230.71(A) service shall have max 6 disconnects, talked to contr 4/4/2005 1:26:11 PM
|
Electrical Rough-In | 3/30/2005 | 3/31/2005 | 3/31/2005 | P | FAIL |
Bob Reichert
|
|
|
kevin-- ###-#### called left message, 250.92(A)&(B)(4) bonding type locknuts shall be used at service,250.104(A) metal water piping system shall be bonded. Note: locate gndg electrodes 3/31/2005 12:40:18 PM
|
Electrical Rough-In | 3/31/2005 | 3/31/2005 | 3/31/2005 | P | PASS |
Bob Reichert
|
|
|
ric garage only
|
Application received | | | 3/30/2005 | | |
|
|
|
|
Issue & PRINT permit | | | 3/30/2005 | | |
|
|
|
|