Temporary Service | 4/4/2005 | 4/4/2005 | 4/4/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/4/2005 at 6:52:23 AM. Contact: ###-####. corrections made t/s u/g n ok 4/4/2005 7:47:19 AM
|
DOC - Permit Finaled | 4/4/2005 | 4/4/2005 | 4/4/2005 | A | PASS |
Bob Reichert
|
|
|
Finaled by inspector at 4/4/2005 7:47:23 AM
|
Temporary Service | 3/31/2005 | 3/31/2005 | 3/31/2005 | P | FAIL |
Bob Reichert
|
|
|
###-#### - clyle called contr, left message, 250.24(B) bond shall be provided for grounded conductor and grounding electrode conductor to ground lug, 110.12(C) recepts shall not be broken 15A and 50A, 590.6(B)(1) 50A recpt shall have gfci protection. fee due 3/31/2005 5:19:26 PM
|
Issue permit | | | 3/31/2005 | | DONE |
|
|
|
|
Application received | | | 3/31/2005 | | |
|
|
|
|