Final | 6/13/2005 | 6/13/2005 | 6/13/2005 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok to final
|
Electrical Rough-In | 4/26/2005 | 4/27/2005 | 4/27/2005 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer called contr, left corr notice, 210.52(A) (2) rcpt shall be added in 2' wall by fireplace, 300.4(D) nm cable shall be 1 1/4" from edge of framing member by pantry, ric ok kitchen dining area 4/27/2005 12:10:10 PM
|
Electrical Rough-In | 4/13/2005 | 4/14/2005 | 4/14/2005 | A | PART |
Bob Reichert
|
|
|
john ###-#### ric ok for addition only, corr made 4/14/2005 10:36:10 AM
|
Electrical Rough-In | 4/12/2005 | 4/13/2005 | 4/13/2005 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer cor. posted called 300.4(A)(1)&(D), 210.52(A) outlet spacing, 210.70 needs to switch outlide light at new outside exit, update permit for proper number of rooms doing work in 4/13/2005 9:34:30 AM
|
Application received | | | 4/1/2005 | | |
|
|
|
This permit was created on the web by Dana Moyer
|