Final | 6/20/2005 | 6/20/2005 | 6/20/2005 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 6/20/2005 at 7:49:23 AM. Contact: ###-####. called contr, left message, left survey, 210.8(A)(1) bathroom recpt shall be gfci
|
Electrical Rough-In | 4/11/2005 | 4/11/2005 | 4/11/2005 | P | PASS |
Bob Reichert
|
|
|
jerry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corrections made, ric ok 4/11/2005 12:16:05 PM
|
Issue permit | | | 4/11/2005 | | DONE |
|
|
|
|
Electrical Rough-In | 4/8/2005 | 4/8/2005 | 4/8/2005 | P | FAIL |
Bob Reichert
|
|
|
###-#### jerry called, left message, left corr notice. 110.12(A) unused openings shall be closed, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, 334.30 cable shall be secured within 12" of panel,nBCC all make-up shall be done(west side outside),A/C cable not run 4/8/2005 2:56:01 PM
|
Application received | | | 4/8/2005 | | |
|
|
|
|