First Notice Sent | | 4/29/2005 | 5/3/2005 | | DONE |
|
|
|
This permit finaled on the web by Dan Mitchell
|
DOC - Permit Finaled | 4/29/2005 | 4/29/2005 | 4/29/2005 | A | PASS |
Jack Frank
|
|
|
Finaled by inspector at 4/29/2005 8:49:59 AM
|
Final | 4/28/2005 | 4/29/2005 | 4/29/2005 | A | PASS |
Jack Frank
|
|
|
Would like to meet you onsite @ 8:30 AM this morning to inspect your requested corrections.Thanks!!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell ok 4/29/2005 8:48:33 AM
|
Permanent Service | 4/29/2005 | 4/29/2005 | 4/29/2005 | A | PASS |
Jack Frank
|
|
|
p/s u/g rec. ok
|
Final | 4/26/2005 | 4/27/2005 | 4/27/2005 | P | FAIL |
Jack Frank
|
|
|
We replaced the old 200 amp disconnect, replaced an existing receptacle with a GFCI receptacle, replaced some surface- run smurf tube with conduit.Please call me for access and tour.Thanks!!!Dan.; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell cor. grd at p/s shall meet 2005 nec, needs 3/0 from meter to new p/s, high leg orange and B phase, bond hot&cold at both water heaters, bond around metal pipe isolated by plastic pipe with #4 copper isolate grds and neutrals load side of p/s had conference with mitchell elect 4/27/2005 2:16:24 PM
|
Application received | | | 4/22/2005 | | |
|
|
|
|
Issue permit | | | 4/22/2005 | | DONE |
|
|
|
|