Second Notice ELE | 9/9/2005 | 9/9/2005 | 9/14/2005 | | DONE |
|
|
|
This permit finaled on the web by Barbara Szurgot
|
First Notice | 8/15/2005 | 8/15/2005 | 9/9/2005 | | DONE |
Jack Frank
|
|
|
|
Final | 8/15/2005 | 8/15/2005 | 8/15/2005 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot ok card signed
|
Final | 8/10/2005 | 8/11/2005 | 8/11/2005 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot cor.posted called 110.3(B) use manufactures listed breakers only, 110.12(A) seal all unused KOs and breaker openings,BCC no violations to be retained, 408.36(F) back-fed devices shall be install as required
|
Electrical Rough-In | 7/28/2005 | 7/28/2005 | 7/28/2005 | P | PASS |
Jack Frank
|
|
|
upper floor ceiling inspection///doug; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa all ceilings ok and corrections made
|
Electrical Rough-In | 7/25/2005 | 7/26/2005 | 7/26/2005 | A | FAIL |
Jack Frank
|
|
|
Ceiling grid inspection. If not open, lock box is on door to the left of the front door. Key pad 1931.; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot cor. posted called 110.26(F)(1) correction not made needs to remove sprinkler line from above sub panel 1st floor and new violation clearence above panel 2nd floor, remove drain vent and duct or install hard structural ceiling per conversation on 05-15-05
|
Electrical Rough-In | 7/26/2005 | 7/26/2005 | 7/26/2005 | A | PART |
Jack Frank
|
|
|
Ceiling grid inspection. If not open, lock box is on door to the left of the front door. Key pad 1931.; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot ceiling ok for 1st floor only
|
Rough-In Permanent Service | 6/15/2005 | 6/15/2005 | 6/15/2005 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/15/2005 at 7:39:15 AM. Contact: ###-####. walls 1st and 2nd floor ok cor. posted for sub panel shall provide required clearence 110.26(F)(1) sprinkler from above,drain from below
|
Permanent Service | 6/6/2005 | 6/7/2005 | 6/7/2005 | A | PASS |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 6/6/2005 at 11:14:51 AM. Contact: ###-####. p/s o/h n ok
|
Conference | 5/5/2005 | 5/10/2005 | 5/10/2005 | A | PASS |
Mike Kinnear
|
|
|
szurgot electric; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa t/w larry regarding u-pull, angle pull,& straight pull j- box on roof & below sub panals.
|
Application received | | | 5/5/2005 | | |
|
|
|
|
Issue permit | | | 5/5/2005 | | DONE |
|
|
|
|