Final | 6/2/2006 | 6/5/2006 | 6/5/2006 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
Final | 5/12/2006 | 5/15/2006 | 5/15/2006 | A | NR |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 5/12/2006 at 1:29:53 PM. Contact: ###-####. shall install murphy bed , or outlet for wall space
|
Electrical Rough-In | 1/31/2006 | 1/31/2006 | 1/31/2006 | P | PASS |
Mike Kinnear
|
|
|
Paul; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong ok cover ri
|
Electrical Rough-In | 1/26/2006 | 1/27/2006 | 1/27/2006 | A | FAIL |
Jack Frank
|
|
|
Paul -- call 1st before insp; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong cor. do not cover , met owner 210.52(A) outlet spacing everywhere, 210.11(C)(3) bath circuit, 314.17 replace 234 gang boxes broken clamps, 300.4 nail plates 11/4" everywhere
|
Electrical Rough-In | 5/16/2005 | 5/16/2005 | 5/16/2005 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 5/16/2005 at 7:09:00 AM. Contact: ###-####. r/i for stairway only
|
Electrical Rough-In | 5/11/2005 | 5/11/2005 | 5/11/2005 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 5/11/2005 at 6:53:53 AM. Contact: ###-####. cor. and do not cover posted talked with owner, 314.16 box fill, 250.148 pigtail all equip grds at jboxes, staple within 8 or 12 inches of plastic and metal boxes, 300.14 6" free length, splices not made up tight, seal all KOs, and replace plastic boxes with unused KOs note 432 made note of box fil, grd boxes, and 11/4 during conference on 05-09-05 5/11/2005 4:26:01 PM
|
Electrical Rough-In | 5/10/2005 | 5/10/2005 | 5/10/2005 | P | PASS |
William E Thomas
|
|
|
###-#### - paul conf with home owner box fill, 1 1/4 stapling, grounding metal boxes
|
Issue PAID IN FULL permit | | | 5/10/2005 | | DONE |
|
|
|
|
Application received | | | 5/10/2005 | | |
|
|
|
|