Final | 8/18/2005 | 8/18/2005 | 8/18/2005 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/18/2005 at 5:52:56 AM. Contact: ###-####. corrections made, ok to final
|
Final | 8/17/2005 | 8/17/2005 | 8/17/2005 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/17/2005 at 10:16:55 AM. Contact: ###-####. called contr left message,210.52 (C)(2) recpt shall be installed in island within 2' of sink, 210.52(C)(5) recpt shall not be located where counter-top extends 6" beyond it's support base, 440.12 ac disconnect shall match nameplate on ac, 408.4 circuit directory shall have sufficient detail to identify each load.
|
Rough-In Permanent Service | 5/13/2005 | 5/16/2005 | 5/16/2005 | A | PASS |
Bob Reichert
|
|
|
rowdy; Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe counted 26, not 16 rooms, ric ok p/s u/g n ok
|
Application received | | | 5/13/2005 | | DONE |
|
|
|
This permit was created on the web by Rowdy Monroe
|