Final | 12/1/2005 | 12/1/2005 | 12/1/2005 | A | PASS |
Jack Frank
|
|
|
ok
|
Final | 11/22/2005 | 11/23/2005 | 11/23/2005 | A | FAIL |
Jack Frank
|
|
|
Call daniel with any questions Happy Thanksgiving!!; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa cor. called 210.52(C)(5) outlet not allowed below counter when there is a backsplash N unit kit left of sink everything else ok
|
Rough-In Permanent Service | 8/5/2005 | 8/5/2005 | 8/5/2005 | P | PASS |
Mike Kinnear
|
|
|
Call francis with any questions , Thanks you jack have a great day.; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa corrections made ok cover ri p/s o/h n ok
|
Rough-In Permanent Service | 7/29/2005 | 7/29/2005 | 7/29/2005 | P | FAIL |
Jack Frank
|
|
|
call francis with any questions ###-####; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa cor. posted called 210.52(A), 210.52 (C), 300.4, also needs updated and approved plans, bond screw at sub panel, and reinstall cables removed by plumber
|
Application received | | | 5/20/2005 | | |
|
|
|
|
Issue permit | | | 5/20/2005 | | DONE |
|
|
|
|