Final | 9/13/2005 | 9/13/2005 | 9/13/2005 | P | PASS |
Bob Reichert
|
|
|
mike ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie corr made, ok to final
|
Final | 9/9/2005 | 9/9/2005 | 9/9/2005 | P | FAIL |
Bob Reichert
|
|
|
mike ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, left corr notice, 404.9(A) switch faceplate shall seat against finished surface,210.52(A)(2)recpt shall be installed in wallspace over 2', 680.73 tub shall have access hatch, 352.30(A)rnc shall be strapped within 3' of meter
|
Electrical Rough-In | 5/24/2005 | 5/24/2005 | 5/24/2005 | P | PASS |
Bob Reichert
|
|
|
###-#### - mike called contr, left survey, 300.4(D) nm cable shall be 1 1/4" from edge of framing member, BCC all make-up to be done, recpt on N side garage, job id sticker shall be posted
|
Issue permit | | | 5/24/2005 | | DONE |
|
|
|
|
Application received | | | 5/24/2005 | | |
|
|
|
|