Final | 11/2/2006 | 11/3/2006 | 11/3/2006 | A | PASS |
Bob Reichert
|
|
|
Contact is Todd Stewart. Corrections for final.; Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA corr made, ok to final
|
Final | 10/31/2006 | 11/1/2006 | 11/1/2006 | A | FAIL |
Bob Reichert
|
|
|
Contact:Todd Stewart; Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA called contr, left corr notice, nec 210.8(A)(3) outdoor recpts shall be gfci protected, 210.52(B)(1) no outside recpts shall be connected to small appliance branch circuits, 210.70(A)(2) exterior door of garage shall have lighting outlet installed and interior also, 110.12(C) there shall be no broken parts (garage), 440.21 a/c disconnects shall not exceed mfgrs listed nameplate for overcurrent,210.52(E) shall install recpt at rear of dwelling
|
Rough-In Permanent Service | 11/11/2005 | 11/14/2005 | 11/14/2005 | A | PASS |
Jack Frank
|
|
|
Corrections have been made. Contact Harvey Reyna.; Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA p/s o/h new ok
|
Rough-In Permanent Service | 11/9/2005 | 11/10/2005 | 11/10/2005 | A | PART |
Jack Frank
|
|
|
Corrections. Contact Harvey Reyna.; Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA r/i ok only cor posted 230.24(A( exception #3 needs 18" from drip loop to roof, 314.20 outside boxes shall be flush with siding called
|
Rough-In Permanent Service | 11/7/2005 | 11/8/2005 | 11/8/2005 | A | FAIL |
Jack Frank
|
|
|
Contact Harvey Reyna; Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA cor. called reinspection fee 210.52(A) outlet spacing, 312.5 needs conn. in garage for cable, 250.24&32 terminate GEC to neutral bus and install bond screw
|
Stop Work/Reinspection Fee | 11/8/2005 | 11/8/2005 | 11/8/2005 | A | DONE |
Jack Frank
|
|
|
Contact Harvey Reyna; Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA reinspection fee due too many inspections on job with corrections
|
Rough-In Permanent Service | 11/7/2005 | 11/7/2005 | 11/7/2005 | P | NR |
Mike Kinnear
|
|
|
Contact Harvey Reyna.; Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA called t/w harvey he needs to meet with jack regarding this inspections. he okay with that.
|
Final | 6/22/2005 | 6/22/2005 | 6/22/2005 | P | CANC |
Jack Frank
|
|
|
harvey Note: outside partial wall inspection and incase grounding in concrete; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles needed r/i
|
Electrical Rough-In | 6/22/2005 | 6/22/2005 | 6/22/2005 | P | PART |
Jack Frank
|
|
|
harvey Note: outside partial wall inspection and incase grounding in concrete; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles electrode ok for dirt, and exterior walls ok only
|
Electrical Rough-In | 6/14/2005 | 6/14/2005 | 6/14/2005 | P | FAIL |
Jack Frank
|
|
|
partial -harvey--also uffer ground ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie cor. posted called 300.4, 314.20 2 gang din rm, 210.52(A)(B) outlet spacing din rm
|
Electrical Rough-In | 6/14/2005 | 6/14/2005 | 6/14/2005 | P | PART |
Jack Frank
|
|
|
partial -harvey--also uffer ground ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie concrete encased electrode ok for concrete, and u/g ok only no r/i for house
|
Electrical Rough-In | 6/1/2005 | 6/1/2005 | 6/1/2005 | P | FAIL |
Jack Frank
|
|
|
harvey; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called needs approved plans , 300.4 (A)(1)&(D) 210.52(A) apcing, 314.20 boxes set back
|
Electrical Rough-In | 5/25/2005 | 5/26/2005 | 5/26/2005 | A | FAIL |
Jack Frank
|
|
|
###-#### - harvey Note: partial for outer wall not ready make not complete box fill, called left message
|
Application received | | | 5/25/2005 | | |
|
|
|
|
Issue permit | | | 5/25/2005 | | |
|
|
|
|