Third Notice ELE | 1/12/2006 | 1/12/2006 | 1/13/2006 | | DONE |
|
|
|
This permit finaled on the web by Daniel Gamboa
|
Second Notice ELE | 12/28/2005 | 12/28/2005 | 1/12/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 12/16/2005 | 12/16/2005 | 12/28/2005 | | DONE |
Pat Lass
|
|
|
|
Final | 12/15/2005 | 12/16/2005 | 12/16/2005 | A | PASS |
Pat Lass
|
|
|
Made corrections please call James at ###-#### with any questions.; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa signed inspection record card
|
Final | 12/14/2005 | 12/15/2005 | 12/15/2005 | A | FAIL |
Bob Reichert
|
|
|
Final inspection call James with any questions.; Phone #: ###-#### Internet Inspection Request from: Daniel Gamboa called contr, left corr notice, 408.4 circuit directory shall be provided for individual bkrs, 250.104(A)(1) shall bon hot and cold water lines, 358.30 emt shall be supported within 3' of panel,410.3 lens cover shall be installed for fixtures by elev,352.30 rnc shall be strapped at service
|
Final | 12/13/2005 | 12/14/2005 | 12/14/2005 | A | NR |
Jack Frank
|
|
|
james ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called needs covers for all j boxes
|
Permanent Service | 11/7/2005 | 11/8/2005 | 11/8/2005 | A | FAIL |
Pat Lass
|
|
|
james; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 230.7 110.12(c) dead front bent and unable to be properly installed.
|
Temporary Service | 10/12/2005 | 10/12/2005 | 10/12/2005 | P | CANC |
Pat Lass
|
|
|
james///please call regarding correction notice; Phone #: ###-#### Internet Inspection Request from: Barbara Moore this is by special agreement per J. Schmer 20 days P/S
|
Permanent Service | 10/12/2005 | 10/12/2005 | 10/12/2005 | P | PASS |
Pat Lass
|
|
|
james///please call regarding correction notice; Phone #: ###-#### Internet Inspection Request from: Barbara Moore this is to be energized for a maximum of 20 days for limited use afthe which the required disconnect will be installed P/S U/G N Ok for power for 20 days Per J.Schmer
|
Rough-In Permanent Service | 9/16/2005 | 9/19/2005 | 9/19/2005 | A | FAIL |
Pat Lass
|
|
|
james; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa 230.2 only one service 230.72 grouping of disconnects. 110.3 install factory MBJ GEC to connect to neutral
|
Electrical Rough-In | 9/16/2005 | 9/16/2005 | 9/16/2005 | P | CANC |
Pat Lass
|
|
|
james; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
Electrical Rough-In | 9/6/2005 | 9/6/2005 | 9/6/2005 | P | PASS |
Bob Reichert
|
|
|
underground parking lot lights.###-#### Dennis ok to cover u/g for parking lot lights except west 1/2. gave ok to cover 10' from last west light in driveway to prevent entry from being blocked
|
Electrical Rough-In | 9/2/2005 | 9/2/2005 | 9/2/2005 | P | PASS |
William E Thomas
|
|
|
stairwells only ---james; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie stairwells-walls and hardlid ok entryway-walls only ok underground for pole lights ok
|
Electrical Rough-In | 8/11/2005 | 8/12/2005 | 8/12/2005 | A | PART |
Pat Lass
|
|
|
cover inspection for canopy only///james; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|
Electrical Rough-In | 6/17/2005 | 6/17/2005 | 6/17/2005 | P | PART |
Pat Lass
|
|
|
underground inspection please///don; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
Electrical Rough-In | 6/8/2005 | 6/8/2005 | 6/8/2005 | P | PART |
Pat Lass
|
|
|
upher ground inspection please////###-#### dennis
|
Issue permit | | | 6/8/2005 | | DONE |
|
|
|
|
Application received | | | 6/8/2005 | | |
|
|
|
|