Permit NumberELE05-02038
StatusFinaled
Name S K ELECTRIC
Site Address 9740 W CORY LN
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/8/20058/8/20058/8/2005PPASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 8/8/2005 at 9:57:40 AM. Contact: ###-####. ok final
Rough-In Permanent Service6/13/20056/14/20056/14/2005APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 6/13/2005 at 5:52:06 PM. Contact: ###-####. corrections made, ric ok , p/s u/g n ok
Rough-In Permanent Service6/9/20056/10/20056/10/2005AFAIL
DetailsBob Reichert
shawn ###-#### called, left message, left corr notice, 300.4(A)(1) edge of hole shall be 1 1/4" from edge of framing member, 300.4(B) (D) nm cable shall be 1 1/4" from edge of framing member, 312.5 gec shall have abrasion protection, 110.12(A) box shall have un-used openings closed,210.52(C)(10 kitchen outlets shall be max 24", 210.52(H) hall shall have recpt if over 10',210.52(A)(2) 2' wall shall have recpt by utility, dining room, 334.80 shall derate bundled cable over panel, 110.14(A) terms for more than 1 conductor shall be identified,BCC job id sticker shall be posted, approved set of plans shall be on job
Issue permit  6/9/2005 DONE
Application received  6/9/2005