Second Notice ELE | 7/13/2005 | 7/13/2005 | 7/25/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 6/22/2005 | 7/13/2005 | | DONE |
|
|
|
|
Final | 6/22/2005 | 6/22/2005 | 6/22/2005 | P | PASS |
Mike Kinnear
|
|
|
Ready for Final inspection @ request of inspector. Thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corrections made etl did feild evaluation ok final
|
Electrical Rough-In | 6/9/2005 | 6/10/2005 | 6/10/2005 | A | FAIL |
Jack Frank
|
|
|
Please meet with Scott or Chuck (####-####) They will show you the new machine and any other work that needs inspected. Thank you.; Phone #:###-#### Internet Inspection Request from: BRIAN KEITH cor. posted called 314.23(H)(1) shall use boxes with hubs for pendant boxes, 110.2 equip shall be listed, 250.97 shall use bond bushing where concentric, eecentric KOs and encounted for bonding over 250 volts to grd, 408.4 label all circuits at panels and switchboards
|
Application received | | | 6/9/2005 | | |
|
|
|
|
Issue permit | | | 6/9/2005 | | DONE |
|
|
|
|