Final | 9/9/2005 | 9/9/2005 | 9/9/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/9/2005 at 7:16:23 AM. Contact: ###-####. ok to final
|
Electrical Rough-In | 6/22/2005 | 6/22/2005 | 6/22/2005 | P | PASS |
Bob Reichert
|
|
|
dino ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles talked to elect, told to remove gnd from south sub-panel that comes from conc enc electrode. ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 6/20/2005 | 6/21/2005 | 6/21/2005 | A | FAIL |
Bob Reichert
|
|
|
dean-- ###-#### called contr, left corr notice, 250.24(A) gec shall be connected to grounded service conductor at service
|
Issue & PRINT permit | | | 6/20/2005 | | |
|
|
|
|
Application received | | | 6/20/2005 | | |
|
|
|
|