Second Notice ELE | 11/21/2005 | 11/21/2005 | 11/29/2005 | | DONE |
|
|
|
This permit finaled on the web by Jeff Radford
|
First Notice | 11/10/2005 | 11/10/2005 | 11/21/2005 | | DONE |
Bob Reichert
|
|
|
|
Final | 11/10/2005 | 11/10/2005 | 11/10/2005 | A | PASS |
Bob Reichert
|
|
|
corrections made, no card to sign, ok to final
|
Electrical Rough-In | 10/22/2005 | 10/24/2005 | 10/24/2005 | A | CANC |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/22/2005 at 1:24:38 PM. see final
|
Final | 10/24/2005 | 10/24/2005 | 10/24/2005 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/22/2005 at 1:24:38 PM. signed t/o card, left corr notice, 110.3 shall not use cords for permanently installed equipment
|
Final | 10/18/2005 | 10/19/2005 | 10/19/2005 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/18/2005 at 7:49:35 PM. Contact: ###-####. met contr, left corr notice, 210.8(B)(2) all 15 and 20A recpts in kitchen shall have gfci protection
|
Electrical Rough-In | 10/13/2005 | 10/14/2005 | 10/14/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/13/2005 at 11:32:13 AM. Contact: ###-####. rooftop units ok, noted on plan. wrote correction notice, 410.4(A) fixtures shall be marked suitable for wet locations for outside sconces
|
Electrical Rough-In | 10/11/2005 | 10/12/2005 | 10/12/2005 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/11/2005 at 2:45:18 PM. Contact: ###-####. part of kitchen, bar, and dining room ok. will finish later. (Done as part final.)
|
Electrical Rough-In | 9/29/2005 | 9/29/2005 | 9/29/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/29/2005 at 6:51:02 AM. Contact: ###-####. center section dining room clg ok to cover
|
Electrical Rough-In | 9/26/2005 | 9/26/2005 | 9/26/2005 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/26/2005 at 6:50:10 AM. Contact: ###-####. dining room east and west clg cover anop
|
Electrical Rough-In | 9/22/2005 | 9/23/2005 | 9/23/2005 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/22/2005 at 4:11:27 PM. Contact: ###-####. sw part ok to cover, main dining area, but ok to cover as needed, will see again.
|
Electrical Rough-In | 9/21/2005 | 9/21/2005 | 9/21/2005 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/21/2005 at 6:44:09 AM. Contact: ###-####. ok to cover ceiling except where panels located, kitcen area only, wrote correction notice 110.26(F)(1)(b) protection shall be provided in dedicated space to avoid damage to elect equip, left with foreman
|
Electrical Rough-In | 9/19/2005 | 9/20/2005 | 9/20/2005 | A | NR |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 9/19/2005 at 3:38:39 PM. Contact: ###-####. no support wires
|
Electrical Rough-In | 9/9/2005 | 9/12/2005 | 9/12/2005 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 9/9/2005 at 2:37:26 PM. Contact: ###-####. ANOP
|
Electrical Rough-In | 8/31/2005 | 9/1/2005 | 9/1/2005 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/31/2005 at 2:26:59 PM. Contact: ###-####. anop
|
Electrical Rough-In | 8/26/2005 | 8/30/2005 | 8/30/2005 | P | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/26/2005 at 7:31:51 AM. Contact: ###-####.
|
Permanent Service | 8/26/2005 | 8/26/2005 | 8/26/2005 | P | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/26/2005 at 7:32:14 AM. Contact: ###-####. P/S U/G N Ok
|
Electrical Rough-In | 8/22/2005 | 8/22/2005 | 8/22/2005 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/22/2005 at 10:24:59 AM. Contact: ###-####. anop
|
Electrical Rough-In | 8/15/2005 | 8/16/2005 | 8/16/2005 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/15/2005 at 4:55:56 PM. Contact: ###-####. anop
|
Electrical Rough-In | 8/10/2005 | 8/10/2005 | 8/10/2005 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/10/2005 at 10:41:19 AM. Contact: ###-####. anop
|
Electrical Rough-In | 8/1/2005 | 8/1/2005 | 8/1/2005 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/1/2005 at 9:19:36 AM. Contact: ###-####. anop
|
Electrical Rough-In | 7/26/2005 | 7/26/2005 | 7/26/2005 | A | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 7/26/2005 at 7:13:04 AM. Contact: ###-####. ANOP
|
Electrical Rough-In | 7/21/2005 | 7/21/2005 | 7/21/2005 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 7/21/2005 at 7:35:45 AM. Contact: ###-####. kitchen area walls ok
|
Electrical Rough-In | 7/14/2005 | 7/14/2005 | 7/14/2005 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 7/14/2005 at 7:05:24 AM. Contact: (208) monument lights ok
|
Electrical Rough-In | 7/6/2005 | 7/7/2005 | 7/7/2005 | A | PASS |
Bob Reichert
|
|
|
PF changs//romar electric; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa north 1/2 ok to pour
|
Electrical Rough-In | 6/29/2005 | 6/29/2005 | 6/29/2005 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 6/29/2005 at 10:53:00 AM. Contact: ###-####. anop
|
Owner Supplied Equipment | | | 6/22/2005 | | |
|
|
|
|
Application received | | | 6/22/2005 | | DONE |
|
|
|
This permit was created on the web by Jeff Radford
|