Second Notice ELE | 12/26/2006 | 12/26/2006 | 1/4/2007 | | DONE |
|
|
|
This permit finaled on the web by Sandee Johnson
|
First Notice | 10/6/2006 | 10/6/2006 | 12/26/2006 | | DONE |
Bob Reichert
|
|
|
|
Final | 10/5/2006 | 10/6/2006 | 10/6/2006 | A | PASS |
Bob Reichert
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, ok to final, no card to sign
|
ELE-Aging Inspection | 10/5/2006 | 10/5/2006 | 10/5/2006 | | DONE |
Bob Reichert
|
|
|
called contr, they will call for final, apparently motors relocated and rewired
|
ELE-Aging Inspection | 8/4/2006 | 8/4/2006 | 8/4/2006 | | NR |
Bob Reichert
|
|
|
checked with contr, still needs to relocate vac motors
|
ELE-Aging Inspection | 5/29/2006 | 5/29/2006 | 5/30/2006 | | NR |
Bob Reichert
|
|
|
called contr, motors out of service and disconnected, supposed to move to new room.
|
Conference | 3/27/2006 | 3/27/2006 | 3/27/2006 | P | DONE |
Bob Reichert
|
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles looked at vacuum motors for theater, there are no listing marks, and junction box retrofit is not satisfactory, will meet 324 to review for next step.
|
ELE-Aging Inspection | 2/10/2006 | 2/10/2006 | 2/10/2006 | | DONE |
Bob Reichert
|
|
|
suc
|
Final | 10/28/2005 | 10/31/2005 | 10/31/2005 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/28/2005 at 3:19:09 PM. Contact: ###-####. signed t/o card, left corr notice, 110.3 atm and screen lifts shall be listed408.5 panel schedules shall be in place, lv transformers and boxes shall be closed and bushings in boxes
|
Electrical Rough-In | 10/22/2005 | 10/24/2005 | 10/24/2005 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/22/2005 at 1:21:14 PM. Contact: ###-####. ok to cover clg anop
|
Electrical Rough-In | 10/13/2005 | 10/14/2005 | 10/14/2005 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/13/2005 at 4:32:04 PM. Contact: ###-####. front soffits ok to cover
|
Electrical Rough-In | 10/6/2005 | 10/7/2005 | 10/7/2005 | A | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/6/2005 at 3:02:09 PM. upper level wall ok to cover anop
|
Electrical Rough-In | 10/5/2005 | 10/5/2005 | 10/5/2005 | P | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 10/5/2005 at 9:53:40 AM. Contact: ###-####. ok to cover entry way to ticket counters clg and part of stair walls anop
|
Electrical Rough-In | 9/30/2005 | 9/30/2005 | 9/30/2005 | P | PART |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/30/2005 at 7:57:58 AM. Contact: ###-####. ok to cover walls box office area,anop
|
Electrical Rough-In | 9/26/2005 | 9/26/2005 | 9/26/2005 | P | PART |
Bob Reichert
|
|
|
kendall- ceiling insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie clg cover main area, kitchen, entry to theaters ok anop, should be all of clgs, 2nd floor
|
Override - Parcel Holds | 1/1/1900 | 1/1/1900 | 9/26/2005 | | |
|
|
|
need ele insp
|
Electrical Rough-In | 9/12/2005 | 9/13/2005 | 9/13/2005 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 9/12/2005 at 4:43:11 PM. Contact: ###-####. anop
|
Electrical Rough-In | 9/12/2005 | 9/12/2005 | 9/12/2005 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 9/12/2005 at 6:36:26 AM. Contact: ###-####. anop
|
Electrical Rough-In | 9/7/2005 | 9/8/2005 | 9/8/2005 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 9/7/2005 at 1:00:47 PM. Contact: ###-####. anop #4's in wireways have been changed to #6's
|
Electrical Rough-In | 8/31/2005 | 9/1/2005 | 9/1/2005 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/31/2005 at 2:39:50 PM. Contact: ###-####. anop
|
Electrical Rough-In | 8/24/2005 | 8/25/2005 | 8/25/2005 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/24/2005 at 3:06:35 PM. Contact: ###-####. anop
|
Electrical Rough-In | 8/23/2005 | 8/23/2005 | 8/23/2005 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/23/2005 at 7:39:10 AM. Contact: ###-####. partial stairwells borders ok
|
Electrical Rough-In | 8/16/2005 | 8/17/2005 | 8/17/2005 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 8/16/2005 at 3:40:20 PM. Contact: ###-####. u/g and 1 wall anop
|
Electrical Rough-In | 8/15/2005 | 8/15/2005 | 8/15/2005 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/15/2005 at 8:26:53 AM. Contact: ###-####. anopleft correction for cords above ceiling
|
Electrical Rough-In | 8/12/2005 | 8/12/2005 | 8/12/2005 | P | PART |
Pat Lass
|
|
|
###-#### Scheduled by a contractor via Hello! on 8/12/2005 at 8:00:48 AM. Contact: ###-####. boarders ok in mezinene
|
Electrical Rough-In | 8/10/2005 | 8/10/2005 | 8/10/2005 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/10/2005 at 10:40:16 AM. Contact: ###-####. anop
|
Electrical Rough-In | 8/8/2005 | 8/8/2005 | 8/8/2005 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/8/2005 at 7:38:30 AM. Contact: ###-####. anop
|
Electrical Rough-In | 8/4/2005 | 8/5/2005 | 8/5/2005 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/4/2005 at 2:51:31 PM. Contact: ###-####. anop
|
Permanent Service | 8/4/2005 | 8/5/2005 | 8/4/2005 | A | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/4/2005 at 2:51:55 PM. Contact: ###-####. P/S U/G N Ok
|
Electrical Rough-In | 8/2/2005 | 8/3/2005 | 8/3/2005 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/2/2005 at 3:43:34 PM. Contact: ###-####. anop left correction pull box is not a gutter
|
Permanent Service | 8/3/2005 | 8/3/2005 | 8/3/2005 | P | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 8/2/2005 at 3:43:34 PM. Contact: ###-####. P/S U/G N Ok house meter
|
Electrical Rough-In | 7/29/2005 | 7/29/2005 | 7/29/2005 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 7/29/2005 at 9:03:29 AM. Contact: ###-####. anop
|
Electrical Rough-In | 7/26/2005 | 7/26/2005 | 7/26/2005 | A | PASS |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 7/26/2005 at 7:12:00 AM. Contact: ###-####. ANOP
|
Electrical Rough-In | 7/22/2005 | 7/22/2005 | 7/22/2005 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 7/22/2005 at 11:05:00 AM. Contact: ###-####. anop
|
Electrical Rough-In | 7/21/2005 | 7/21/2005 | 7/21/2005 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 7/21/2005 at 7:33:31 AM. Contact: ###-####. ANOP
|
Electrical Rough-In | 7/20/2005 | 7/20/2005 | 7/20/2005 | A | PART |
Pat Lass
|
|
|
###-#### Scheduled by a contractor via Hello! on 7/20/2005 at 7:06:18 AM. Contact: ###-####. ANOP theaters requires clareification on ceiling wires
|
Electrical Rough-In | 7/19/2005 | 7/19/2005 | 7/19/2005 | P | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 7/19/2005 at 8:31:50 AM. Contact: ###-####. anop
|
Electrical Rough-In | 6/29/2005 | 7/1/2005 | 7/1/2005 | A | PART |
William E Thomas
|
|
|
Scheduled by a contractor via Hello! on 6/29/2005 at 10:54:52 AM. Contact: ###-####. as noted on prints
|
Electrical Rough-In | 6/24/2005 | 6/24/2005 | 6/24/2005 | P | PASS |
Jim Schmer
|
|
|
Scheduled by a contractor via Hello! on 6/24/2005 at 9:16:58 AM. Contact: ###-####. theater back wall, ok - jms
|
Owner Supplied Equipment | | | 6/23/2005 | | |
|
|
|
|
Application received | | | 6/23/2005 | | DONE |
|
|
|