Third Notice ELE | 10/26/2005 | 10/26/2005 | 10/26/2005 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 10/12/2005 | 10/12/2005 | 10/26/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | | 7/19/2005 | 10/12/2005 | | DONE |
|
|
|
|
Final | 7/18/2005 | 7/19/2005 | 7/19/2005 | A | PASS |
Jack Frank
|
|
|
p/s inspection passed, can this be finaled? LEM(Tisha) ok
|
Permanent Service | 6/30/2005 | 6/30/2005 | 6/30/2005 | P | PASS |
Jack Frank
|
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa p/s o/h rec. ok
|
Permanent Service | 6/28/2005 | 6/28/2005 | 6/28/2005 | P | FAIL |
Jack Frank
|
|
|
mike0 ###-#### cor. posted called, 110.26 clearence ,250.66 size grds and bonds , 250.24 (A)(1) terminate grds and bonds at neutral bus, 250.52(A)(1) or 104 (A)(1) grd or bond water system, 250.53(B) grd rod shall be 6ft apart
|
Issue & PRINT permit | | | 6/28/2005 | | |
|
|
|
|
Application received | | | 6/28/2005 | | |
|
|
|
|