Permanent Service | 7/1/2005 | 7/1/2005 | 7/1/2005 | P | PASS |
Jack Frank
|
|
|
harvey; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa p/s o/h rec. ok
|
Final | 7/1/2005 | 7/1/2005 | 7/1/2005 | P | PASS |
Jack Frank
|
|
|
harvey; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
|
Permanent Service | 6/30/2005 | 6/30/2005 | 6/30/2005 | P | FAIL |
Jack Frank
|
|
|
###-####; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles shall remove GEC from raceway and jbox that branch circuits, and feeders are installed in, called
|
Permanent Service | 6/29/2005 | 6/29/2005 | 6/29/2005 | P | FAIL |
Jack Frank
|
|
|
###-#### - harvey Note: 100 ump cor. posted 200.6 no ID 6 or smaller, 250.92(A)(3) bond both ends raceway for GEC,334.46 bushings for rigid, 408.36(F),408.4 sub panel
|
Issue permit | | | 6/29/2005 | | DONE |
|
|
|
|
Application received | | | 6/29/2005 | | |
|
|
|
|