Permanent Service | 7/5/2005 | 7/5/2005 | 7/5/2005 | P | PASS |
Mike Kinnear
|
|
|
dave; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa p/s o/h n ok
|
Final | 7/5/2005 | 7/5/2005 | 7/5/2005 | P | PASS |
Mike Kinnear
|
|
|
dave; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok final this for service only
|
Permanent Service | 6/29/2005 | 6/30/2005 | 6/30/2005 | A | FAIL |
Jack Frank
|
|
|
dave ###-#### cor. p[osted called 250.52(A)(1) and 250.66, shall bond to make water system electrically continuous , remove GEC from conduit for SER cable, and size to table 250.66
|
Issue permit | | | 6/29/2005 | | DONE |
|
|
|
|
Application received | | | 6/29/2005 | | |
|
|
|
|