Final | 10/20/2005 | 10/20/2005 | 10/20/2005 | | DONE |
|
|
|
Final approved per Bob Reichert
|
DOC - C/O Approved | 10/20/2005 | 10/20/2005 | 10/20/2005 | | DONE |
|
|
|
|
DOC - Permit Finaled | | | 10/20/2005 | | |
|
|
|
|
Change Status to I | | | 10/20/2005 | | |
|
|
|
|
Second Notice ELE | 10/12/2005 | 10/12/2005 | 10/14/2005 | | DONE |
|
|
|
This permit value was finaled on the web by Nikki Day
|
First Notice | 9/7/2005 | 9/7/2005 | 10/12/2005 | | DONE |
Bob Reichert
|
|
|
|
Final | 9/7/2005 | 9/7/2005 | 9/7/2005 | P | PART |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Nikki Day signed t/o card. The X-Ray machine has been removed from the premises. The elect will wire the unit and then call for an inspection. The owner has started the process for a field evaluation. He can't use the machine, until it passes the evaluation.
|
Final | 9/5/2005 | 9/6/2005 | 9/6/2005 | A | PART |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Nikki Day ceiling ok to cover, recpts and elect checked out, met elect and wrote corr notice BCC and NEC 110.2 Equip shall be listed and suitable for installation.
|
Final | 9/1/2005 | 9/2/2005 | 9/2/2005 | A | NR |
Bob Reichert
|
|
|
Request for temp occupancy.; Phone #: ###-#### Internet Inspection Request from: Nikki Day checked plugs except se offices, clg nr, equip not installed, no card signed
|
Permanent Service | 8/31/2005 | 8/31/2005 | 8/31/2005 | P | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Nikki Day this is for suite #110 p/s u/g n ok
|
Permanent Service | 8/30/2005 | 8/30/2005 | 8/30/2005 | P | FAIL |
Mike Kinnear
|
|
|
Service and Cieling Inspection; Phone #: ###-#### Internet Inspection Request from: Bryan Atkins service no addess on main panal ( lables)
|
Electrical Rough-In | 7/27/2005 | 7/27/2005 | 7/27/2005 | P | PART |
Jack Frank
|
|
|
Rough-in walls; Phone #: ###-#### Internet Inspection Request from: Nikki Day walls ok
|
Electrical Rough-In | 7/8/2005 | 7/11/2005 | 7/11/2005 | A | PASS |
Bob Reichert
|
|
|
Underslab Inspection; Phone #: ###-#### Internet Inspection Request from: Nikki Day left correction notice for friday,517.13(A) all branch circuits serving patient care areas shall be in metal raceways. u/g ok to pour
|
Electrical Rough-In | 7/8/2005 | 7/8/2005 | 7/8/2005 | P | NR |
Bob Reichert
|
|
|
Underslab Inspection; Phone #: ###-#### Internet Inspection Request from: Nikki Day neede to recall
|
Application received | | | 7/8/2005 | | DONE |
|
|
|
This permit was created on the web by Nikki Day
|