Second Notice ELE | 10/26/2005 | 10/26/2005 | 11/1/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 10/4/2005 | 10/4/2005 | 10/26/2005 | | DONE |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 10/3/2005 | 10/3/2005 | 10/4/2005 | | PASS |
Jack Frank
|
|
|
|
DOC - Permit Finaled | 10/4/2005 | 10/4/2005 | 10/4/2005 | P | PASS |
Jack Frank
|
|
|
|
Second Notice ELE | 8/3/2005 | 8/3/2005 | 8/9/2005 | | DONE |
|
|
|
Not fianled yet
|
First Notice | 7/15/2005 | 7/15/2005 | 8/3/2005 | | DONE |
William E Thomas
|
|
|
|
Permanent Service | 8/1/2005 | 8/1/2005 | 8/1/2005 | P | PASS |
William E Thomas
|
|
|
terry; Phone #: ###-#### Internet Inspection Request from: Letitia p/s u/g n ok
|
Final | 7/29/2005 | 8/1/2005 | 8/1/2005 | A | FAIL |
Jack Frank
|
|
|
terry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. called all violations not made, needs to install factory bonding jumper meterbase
|
Change Status to I | | | 7/29/2005 | | DONE |
|
|
|
Re-open per Jack Frank///7/29/05 BAS
|
Final | 7/27/2005 | 7/27/2005 | 7/27/2005 | P | FAIL |
Jack Frank
|
|
|
per your request cor. posted called 250.24(C) grounded contuctor shall be brought to p/s disconnect, 110.3(B) manufactures instructions states min 2/0 copper, listing problem? call terry ###-####
|
Final | 7/14/2005 | 7/15/2005 | 7/15/2005 | A | PASS |
William E Thomas
|
|
|
terry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s u/g n ok
|
Application received | | | 7/14/2005 | | |
|
|
|
|
Issue permit | | | 7/14/2005 | | DONE |
|
|
|
|