Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberELE05-02516
StatusFinaled
Name PRECISION PUMPING SYSTEMS
Site Address 2825 W MALAD
Project Name 
Customer NumberC-28103
ePlanReview 
Description
shoshone park - install pump and control panel per initial cert of value $18,106///7/14/05 LEM///Final cert value $18,106.00 10/27/2005 cmc
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Second Notice ELE10/26/200510/26/200511/1/2005 DONE
First Notice has not been responded to.
First Notice10/4/200510/4/200510/26/2005 DONE
DetailsJack Frank
ELE-Aging Inspection10/3/200510/3/200510/4/2005 PASS
DetailsJack Frank
DOC - Permit Finaled10/4/200510/4/200510/4/2005PPASS
DetailsJack Frank
Second Notice ELE8/3/20058/3/20058/9/2005 DONE
Not fianled yet
First Notice7/15/20057/15/20058/3/2005 DONE
DetailsWilliam E Thomas
Permanent Service8/1/20058/1/20058/1/2005PPASS
DetailsWilliam E Thomas
terry; Phone #: ###-#### Internet Inspection Request from: Letitia
p/s u/g n ok
Final7/29/20058/1/20058/1/2005AFAIL
DetailsJack Frank
terry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. called all violations not made, needs to install factory bonding jumper meterbase
Change Status to I  7/29/2005 DONE
Re-open per Jack Frank///7/29/05 BAS
Final7/27/20057/27/20057/27/2005PFAIL
DetailsJack Frank
per your request cor. posted called 250.24(C) grounded contuctor shall be brought to p/s disconnect, 110.3(B) manufactures instructions states min 2/0 copper, listing problem? call terry ###-####
Final7/14/20057/15/20057/15/2005APASS
DetailsWilliam E Thomas
terry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
p/s u/g n ok
Application received  7/14/2005  
Issue permit  7/14/2005 DONE