Second Notice ELE | 9/9/2005 | 9/9/2005 | 9/14/2005 | | DONE |
|
|
|
This permit finaled on the web by Barbara Szurgot
|
First Notice | 8/23/2005 | 8/23/2005 | 9/9/2005 | | DONE |
Mike Kinnear
|
|
|
|
Final | 8/22/2005 | 8/23/2005 | 8/23/2005 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot ok final new wiring 324 t/w home owner association & okay old wiring outside for light fixtures.
|
Electrical Rough-In | 7/22/2005 | 7/25/2005 | 7/25/2005 | A | PASS |
Mike Kinnear
|
|
|
trench inspection; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot ok cover under ground rigid conduit
|
Electrical Rough-In | 7/21/2005 | 7/22/2005 | 7/22/2005 | A | FAIL |
Mike Kinnear
|
|
|
Trench inspection. Please call 1/2 hour before inspection so I can get Steve there. Thanks; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot conduit is not 6inch deep nec 300.5 told steve to get them the right depth.
|
Electrical Rough-In | 7/20/2005 | 7/21/2005 | 7/21/2005 | A | NR |
Mike Kinnear
|
|
|
Trench inspection after 9:00 am. Heron Cove condo complex landscape lighting. River Run and River Park crossroads.; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot trench not ready -- note conf with electrician. -- pole base conduit not deep enough for nec table 300.5. uf cable pulled in pvc conduit not approved
|
Application received | | | 7/20/2005 | | |
|
|
|
|
Issue permit | | | 7/20/2005 | | DONE |
|
|
|
|