Third Notice ELE | 3/15/2006 | 3/15/2006 | 3/5/2007 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 2/27/2006 | 2/27/2006 | 3/15/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 2/14/2006 | 2/14/2006 | 2/27/2006 | | DONE |
Bob Reichert
|
|
|
|
ELE-Aging Inspection | 2/14/2006 | 2/14/2006 | 2/14/2006 | | DONE |
Bob Reichert
|
|
|
see final
|
Final | 2/14/2006 | 2/14/2006 | 2/14/2006 | P | PASS |
Bob Reichert
|
|
|
ok to final
|
Final | 7/28/2005 | 7/28/2005 | 7/28/2005 | P | CANC |
Bob Reichert
|
|
|
alex or mat; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see ps
|
Permanent Service | 7/28/2005 | 7/28/2005 | 7/28/2005 | P | PASS |
Bob Reichert
|
|
|
alex or mat; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok for power, called contr to provide abrasion protection for gec, they are coming to move fence. p/s u/g n ok
|
Final | 7/26/2005 | 7/26/2005 | 7/26/2005 | P | NR |
Bob Reichert
|
|
|
kevin or alex; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, too many items for them to review before service or final. they will recall. Items too look for are: Baldor motor and system not listed, 1 ground rod, connector on w/p box not water-tight, job id sticker not posted, panel with drive unit not listed, overcurrent protection to and or from drive not provided, drive panel does not have clear work space, fencing will not leave work space for service panel, 3/4" emt connectors not ul listed as raintight
|
Application received | | | 7/21/2005 | | |
|
|
|
|
Issue permit | | | 7/21/2005 | | DONE |
|
|
|
|