Third Notice ELE | 10/26/2005 | 10/26/2005 | 12/12/2005 | | DONE |
|
|
|
This permit finaled on the web by Ryan Christensen
|
Second Notice ELE | 10/12/2005 | 10/12/2005 | 10/26/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 9/20/2005 | 9/20/2005 | 10/12/2005 | | DONE |
Bob Reichert
|
|
|
|
Final | 9/20/2005 | 9/20/2005 | 9/20/2005 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok to final
|
Final | 8/30/2005 | 8/30/2005 | 8/30/2005 | P | PART |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called contr to make gnd wire green and use 30A Switch for hot water disc. will do final after signs are up. signed occ card
|
Final | 8/29/2005 | 8/30/2005 | 8/30/2005 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called contr,210.8(B)(1) bathroom shall use gfci rcpts,422.31 disc for water heater shall be provided,408.4 panel schedule shall be provided, 250.104 metal water piping shall be bonded
|
Permanent Service | 8/16/2005 | 8/17/2005 | 8/17/2005 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen p/s u/g n ok
|
Permanent Service | 8/16/2005 | 8/17/2005 | 8/16/2005 | A | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Ryan Christensen Inspection cancelled from web by: Ryan Christensen
|
Electrical Rough-In | 8/1/2005 | 8/2/2005 | 8/2/2005 | A | PASS |
William E Thomas
|
|
|
ryan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
Electrical Rough-In | 7/29/2005 | 7/29/2005 | 7/29/2005 | A | FAIL |
Bob Reichert
|
|
|
rough in to cover seth is contact; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen talked to contr, left corr notice, do not cover card on panel. 110.26(F)(1) no piping shall be in dedicated electrical space over meter can, 348.30(A) fmc shall be strapped within 12" of box, 300.4(A)(1) raceways shall be min 1 1/4" from edge of framing member or shall be protected by steel plates
|
Electrical Rough-In | 7/27/2005 | 7/28/2005 | 7/28/2005 | A | PASS |
Bob Reichert
|
|
|
inspect the ufer ground for cover; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen ok to cover gec
|
Electrical Rough-In | 7/27/2005 | 7/27/2005 | 7/27/2005 | P | PASS |
Bob Reichert
|
|
|
underground seth ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok to cover u/g to pole bases and to cover gec
|
Electrical Rough-In | 7/26/2005 | 7/26/2005 | 7/26/2005 | P | CANC |
Mike Kinnear
|
|
|
seth-- underground; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie contractor called canc. inspection
|
Electrical Rough-In | 7/25/2005 | 7/26/2005 | 7/26/2005 | A | PASS |
Bob Reichert
|
|
|
ryan - Note: lightpole bases; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to pour pole bases only. Need to see u/g to bases from source of power.
|
Temporary Service | 7/21/2005 | 7/22/2005 | 7/22/2005 | A | CANC |
Bob Reichert
|
|
|
forman on job is seth woodward; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen wrong permit number
|
Owner Supplied Equipment | | | 7/21/2005 | | |
|
|
|
|
Application received | | | 7/21/2005 | | DONE |
|
|
|
This permit was created on the web by Ryan Christensen
|