Second Notice ELE | 9/14/2005 | 9/14/2005 | 9/15/2005 | | DONE |
|
|
|
This permit finaled on the web by Heather Packer
|
First Notice | 9/1/2005 | 9/1/2005 | 9/14/2005 | | DONE |
Jack Frank
|
|
|
|
Final | 9/1/2005 | 9/1/2005 | 9/1/2005 | A | PASS |
Jack Frank
|
|
|
ok
|
Conference | 8/18/2005 | 8/19/2005 | 8/22/2005 | A | DONE |
Jack Frank
|
|
|
talked with state elevator inspector and electrical contractor will post post correction , light and recept in elevator equip rm shall be dedicated circuit, and terminate flex from new cabinet to equip
|
Final | 8/18/2005 | 8/18/2005 | 8/18/2005 | P | CANC |
Jack Frank
|
|
|
Re-insp.; Phone #: ###-#### Internet Inspection Request from: Heather Packer waiting for information from state elevator inspector, and fire alarm inspector
|
Final | 8/17/2005 | 8/17/2005 | 8/17/2005 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Heather Packer cor called 300.10 needs bond bushing where RE washers are used, 250.148 grd 4sq box, label elevator disconnects, also elevator equip rm all messed up circuit for recept messed up I will address items with owner
|
Application received | | | 7/25/2005 | | DONE |
|
|
|
This permit was created on the web by Heather Packer
|