Final | 8/10/2005 | 8/11/2005 | 8/11/2005 | A | PASS |
Jack Frank
|
|
|
Re-Inspection After Corrections from; Phone #: ###-#### Internet Inspection Request from: Cathy Felin ok
|
Permanent Service | 8/11/2005 | 8/11/2005 | 8/11/2005 | A | PASS |
Jack Frank
|
|
|
Re-Inspection After Corrections from; Phone #: ###-#### Internet Inspection Request from: Cathy Felin p/s o/h rec. ok
|
Final | 8/2/2005 | 8/3/2005 | 8/3/2005 | A | FAIL |
Jack Frank
|
|
|
Final ( NH on 7/29/); Phone #: ###-#### Internet Inspection Request from: Cathy Felin 110.3(B)manufactures instructions no load conductors shall exit top of p/s,250.104(A)(1) bond water with #4, 344.46 bushings for rigid nipples, 110.12(A) seal unused KOs, 250.92(A)(3) choke GEC both ends, or remove emt raceway
|
Final | 7/29/2005 | 8/1/2005 | 8/1/2005 | A | CANC |
Jack Frank
|
|
|
###-#### MARY nOTE: PLEASE CALL 1/2 HR PRIOR TO INSPECTION contractor called and canceled
|
Final | 7/28/2005 | 7/29/2005 | 7/29/2005 | P | NH |
Jack Frank
|
|
|
Phone #: 208-377- x0338 Internet Inspection Request from: Cathy Felin notice posted called also this is a p/s not final, told contractor to request a p/s inspection
|
Application received | | | 7/28/2005 | | DONE |
|
|
|
This permit was created on the web by Cathy Felin
|