Final | 8/18/2006 | 8/18/2006 | 8/18/2006 | P | PASS |
Jack Frank
|
|
|
cw; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok
|
Final | 5/26/2006 | 5/26/2006 | 5/26/2006 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 5/26/2006 at 9:28:54 AM. Contact: ###-####. met owner he added stairs needs lighting and 3 ways for them
|
Final | 1/16/2006 | 1/17/2006 | 1/17/2006 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 1/16/2006 at 9:19:30 PM. Contact: ###-####. cor. posted met owner secure boxes to structure and install all fixtures outside lights, correct wiring recept in garage, needs connectors for cables at ceiling fixtures in garage
|
Electrical Rough-In | 12/6/2005 | 12/7/2005 | 12/7/2005 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/6/2005 at 9:47:45 PM. ok
|
Electrical Rough-In | 12/5/2005 | 12/6/2005 | 12/6/2005 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/5/2005 at 8:38:17 PM. Contact: ###-####. cor. met owner 314.17 staple cable 8" replace all boxes with unused openings, and cutin boxes with broken clamps, 314.16 box fill 334.24 radius of cables, 210.52(A) spacing fam rm
|
Electrical Rough-In | 12/4/2005 | 12/5/2005 | 12/5/2005 | P | NR |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 12/4/2005 at 10:43:38 PM. Contact: (208) called needs to complete all makeup
|
Conference | 11/7/2005 | 11/7/2005 | 11/7/2005 | P | DONE |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 11/7/2005 at 7:48:06 AM. Contact: ###-####.ok
|
Application received | | | 8/1/2005 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 8/1/2005 | | DONE |
|
|
|
|