Final | 9/29/2005 | 9/30/2005 | 9/30/2005 | A | PASS |
Mike Kinnear
|
|
|
Re-inspection on corrections. Internet Inspection Request from: Latisha Peltier corrections made ok final
|
Final | 9/29/2005 | 9/29/2005 | 9/29/2005 | P | FAIL |
Jack Frank
|
|
|
Internet Inspection Request from: Latisha Peltier cor. posted called 410.8 clearence MB closet fixture, 110.3 (A) needs gfci for exhaust fan in shower
|
Rough-In Permanent Service | 8/5/2005 | 8/5/2005 | 8/5/2005 | P | PASS |
Jack Frank
|
|
|
latisha; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa r/i ok p/s u/g new ok
|
Rough-In Permanent Service | 8/4/2005 | 8/5/2005 | 8/5/2005 | A | FAIL |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Latisha Peltier nec 300.4(D) 1 1/4 support cable 314 shall use plastic connector for ground wire in service
|
Electrical Rough-In | 8/3/2005 | 8/3/2005 | 8/3/2005 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 8/3/2005 at 6:17:37 AM. Contact: ###-####. 300.4, 314.16, 300.14, 334.30, 314,17(C) sheath shall extend 1/4 into box, complete all makeup and install boxes in bath rm
|
Application received | | | 8/2/2005 | | |
|
|
|
|
Issue permit | | | 8/2/2005 | | DONE |
|
|
|
|