DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
VOIDED CHANGE STATUS  5/30/2008 DONE
Details
james felton - ###-#### - called to void this permit - he will be hiring someone to do the work
Electrical Rough-In5/8/20065/8/20065/8/2006PFAIL
DetailsJack Frank
JAMES; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
corr. met owner pvc not large enough for wire fill, 300.5T needs 18" deep,, 314.28(A)(3) LB not big enough, 300.4(A)1)&(D) nail plates and 11/4" 334.30,314.17(B) secure nmb and mc within 12" of boxes , 250.53(G) drive grd rods as code states,,352.48 use approved cement for pvc, 250.64(C) no splices in GEC, note complete all wiring and makeup before inspection requested note partial correction only job not ready, told owner if more violations created permit could be voided
ELE-Request for Extension2/9/20062/10/20062/10/2006APASS
DetailsJim Schmer
james; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa extend this one time only JMS
Conference8/3/20058/4/20058/4/2005PDONE
DetailsJack Frank
james ###-#### ok
Application received  8/3/2005  
Issue PAID IN FULL permit  8/3/2005 DONE