VOIDED CHANGE STATUS | | | 5/30/2008 | | DONE |
|
|
|
james felton - ###-#### - called to void this permit - he will be hiring someone to do the work
|
Electrical Rough-In | 5/8/2006 | 5/8/2006 | 5/8/2006 | P | FAIL |
Jack Frank
|
|
|
JAMES; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. met owner pvc not large enough for wire fill, 300.5T needs 18" deep,, 314.28(A)(3) LB not big enough, 300.4(A)1)&(D) nail plates and 11/4" 334.30,314.17(B) secure nmb and mc within 12" of boxes , 250.53(G) drive grd rods as code states,,352.48 use approved cement for pvc, 250.64(C) no splices in GEC, note complete all wiring and makeup before inspection requested note partial correction only job not ready, told owner if more violations created permit could be voided
|
ELE-Request for Extension | 2/9/2006 | 2/10/2006 | 2/10/2006 | A | PASS |
Jim Schmer
|
|
|
james; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa extend this one time only JMS
|
Conference | 8/3/2005 | 8/4/2005 | 8/4/2005 | P | DONE |
Jack Frank
|
|
|
james ###-#### ok
|
Application received | | | 8/3/2005 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 8/3/2005 | | DONE |
|
|
|
|