Temporary Service | 8/27/2005 | 8/29/2005 | 8/29/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/27/2005 at 7:53:56 AM. Contact: ###-####. corrections made, t/s u/g n ok
|
Temporary Service | 8/24/2005 | 8/26/2005 | 8/26/2005 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/24/2005 at 5:18:42 PM. Contact: ###-####. called contr, left corr notice, fee due. 312.5 conductors entering cnclosure shall have abrasion protection, 110.12(C) there shall be no broken parts, 250.56 supplementary ground rod shall be installed (8'-0" long)
|
Temporary Service | 8/3/2005 | 8/8/2005 | 8/3/2005 | A | CANC |
Bob Reichert
|
|
|
steve ###-#### per steve
|
Issue permit | | | 8/3/2005 | | DONE |
|
|
|
|
Application received | | | 8/3/2005 | | |
|
|
|
|