Temporary Service | 8/27/2005 | 8/29/2005 | 8/29/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/27/2005 at 7:53:03 AM. Contact: ###-####. corrections made, t/s u/g n ok
|
Temporary Service | 8/24/2005 | 8/26/2005 | 8/26/2005 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/24/2005 at 5:17:48 PM. Contact: ###-####. called contr, left corr notice 250.24 bonding jumper shall be connected between gec and grounded conductor, 250.53(G) ground rod shall be 8' long and flush with or below ground, 312.5 conductors entering enclosure shall have abrasion protection, fee due
|
Application received | | | 8/4/2005 | | |
|
|
|
|
Issue permit | | | 8/4/2005 | | DONE |
|
|
|
|