Final | 11/1/2005 | 11/2/2005 | 11/2/2005 | A | PASS |
William E Thomas
|
|
|
tom ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
Final | 10/31/2005 | 10/31/2005 | 10/31/2005 | P | FAIL |
Bob Reichert
|
|
|
tom ###-#### called, left message, left corr. notice, 406.4 recpts shall be rigidly secured, 406.4(D) recpts shall project from faceplates or be flush, 210.8(A)(6) kitchen recpts shall have gfci protection, 210.8(A)(2) garage gfci shall operate, 314.23(C) enclosures shall be rigidly mtd and recpts to enclosure
|
Electrical Rough-In | 8/16/2005 | 8/17/2005 | 8/17/2005 | A | PASS |
Bob Reichert
|
|
|
###-#### - tom called contr for ufer ring and some 1 1/4". ric ok , p/s u/g n ok
|
Permanent Service | 8/17/2005 | 8/17/2005 | 8/17/2005 | A | PASS |
Bob Reichert
|
|
|
p/s u/g n ok
|
Application received | | | 8/16/2005 | | |
|
|
|
|
Issue permit | | | 8/16/2005 | | DONE |
|
|
|
|