Telephone call | | | 1/4/2006 | | DONE |
|
|
|
Left message for Dannette to call back regarding final value differences///1/4/06 @1:00pm BAS
|
Telephone call | | | 12/29/2005 | | DONE |
|
|
|
Spoke with Dannett and asked for copy of contract or anything that can prove value discrepancie///12/29/05 @10:20am BAS
|
Third Notice ELE | 11/21/2005 | 11/21/2005 | 12/2/2005 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 11/10/2005 | 11/10/2005 | 11/21/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 10/26/2005 | 10/26/2005 | 11/10/2005 | | DONE |
Bob Reichert
|
|
|
|
Final | 10/26/2005 | 10/26/2005 | 10/26/2005 | A | PASS |
Bob Reichert
|
|
|
per Jim Schmer corrections made, listings ok, ok to final, no card to sign on job site for occupancy
|
Final | 10/21/2005 | 10/21/2005 | 10/23/2005 | P | FAIL |
William E Thomas
|
|
|
danette Note: cube; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles 1. working clearences around panel in confrence room. 2. need to see ul label/listing for office furniture as an assembly.
|
Final | 9/23/2005 | 9/26/2005 | 9/26/2005 | A | PART |
Bob Reichert
|
|
|
please call 30 min prior///daniel or eddie ###-####; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corr notice items ok, clg cover ok, will finish after furniture installed.
|
Final | 9/22/2005 | 9/23/2005 | 9/23/2005 | A | FAIL |
Jack Frank
|
|
|
olga; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. not made called left message 300.11 support wires for cables shall be secured at both ends
|
Final | 9/21/2005 | 9/22/2005 | 9/22/2005 | A | PART |
Jack Frank
|
|
|
olga; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/o ok card signed cor. posted 300.11 needs to install own support for cables and ID them called
|
Final | 9/20/2005 | 9/21/2005 | 9/21/2005 | P | PART |
Bob Reichert
|
|
|
olga; Phone #: ###-#### Internet Inspection Request from: Barbara Moore no card signed, need to see furniture installation to final
|
Electrical Rough-In | 9/15/2005 | 9/16/2005 | 9/16/2005 | A | PASS |
Bob Reichert
|
|
|
ceiling insp - olga; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie corr made, ok to cover ceiling only
|
Electrical Rough-In | 9/13/2005 | 9/14/2005 | 9/15/2005 | P | FAIL |
Bob Reichert
|
|
|
danette; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, told about corr notice , strap emt,cables shall not support cables,support mc cable, close openings in boxes, abandon un-used conduit, 300.11(C), 300.31, 330.30(B), 358.30,110.12(A),BCC
|
Electrical Rough-In | 9/13/2005 | 9/13/2005 | 9/13/2005 | P | NR |
Bob Reichert
|
|
|
ceiling inspection//danette; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa elect said was supposed to be for am tomorrow
|
Electrical Rough-In | 8/30/2005 | 8/31/2005 | 8/31/2005 | A | PART |
Jack Frank
|
|
|
wall inspection//eddie; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa walls ok
|
Electrical Rough-In | 8/30/2005 | 8/30/2005 | 8/30/2005 | P | PART |
Jim Schmer
|
|
|
wall inspection///olga; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa conference on walls only, had smurf and bx cable inside c section of wall.
|
Application received | | | 8/17/2005 | | |
|
|
|
|
Issue permit | | | 8/17/2005 | | DONE |
|
|
|
|