Permit Information
Permit NumberELE05-03021
StatusFinaled
Name SUNSHINE ELECTRIC
Site Address 104 N MILWAUKEE
Project NameTHEATER RETAIL SHOPS
Customer Number 
ePlanReview 
Description
Electrical demolition and new wiring per initial cert of value $3,000///8/17/05 BAS////12/2/2005 - final cert of value $3000 cmc///Per phone call from Leon with Sunshine ELE $3,000 for R/I, $3,000 for Final and $3,500 for Demo & clean up or R/I///1/20/06 BAS
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Telephone call  1/4/2006 DONE
Left message for Dannette to call back regarding final value differences///1/4/06 @1:00pm BAS
Telephone call  12/29/2005 DONE
Spoke with Dannett and asked for copy of contract or anything that can prove value discrepancie///12/29/05 @10:20am BAS
Third Notice ELE11/21/200511/21/200512/2/2005 DONE
Second Notice has not been responded to.
Second Notice ELE11/10/200511/10/200511/21/2005 DONE
First Notice has not been responded to.
First Notice10/26/200510/26/200511/10/2005 DONE
DetailsBob Reichert
Final10/26/200510/26/200510/26/2005APASS
DetailsBob Reichert
per Jim Schmer corrections made, listings ok, ok to final, no card to sign on job site for occupancy
Final10/21/200510/21/200510/23/2005PFAIL
DetailsWilliam E Thomas
danette Note: cube; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
1. working clearences around panel in confrence room.
2. need to see ul label/listing for office furniture as an assembly.
Final9/23/20059/26/20059/26/2005APART
DetailsBob Reichert
please call 30 min prior///daniel or eddie ###-####; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corr notice items ok, clg cover ok, will finish after furniture installed.
Final9/22/20059/23/20059/23/2005AFAIL
DetailsJack Frank
olga; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. not made called left message 300.11 support wires for cables shall be secured at both ends
Final9/21/20059/22/20059/22/2005APART
DetailsJack Frank
olga; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/o ok card signed cor. posted 300.11 needs to install own support for cables and ID them called
Final9/20/20059/21/20059/21/2005PPART
DetailsBob Reichert
olga; Phone #: ###-#### Internet Inspection Request from: Barbara Moore no card signed, need to see furniture installation to final
Electrical Rough-In9/15/20059/16/20059/16/2005APASS
DetailsBob Reichert
ceiling insp - olga; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie corr made, ok to cover ceiling only
Electrical Rough-In9/13/20059/14/20059/15/2005PFAIL
DetailsBob Reichert
danette; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr, told about corr notice , strap emt,cables shall not support cables,support mc cable, close openings in boxes, abandon un-used conduit, 300.11(C), 300.31, 330.30(B), 358.30,110.12(A),BCC
Electrical Rough-In9/13/20059/13/20059/13/2005PNR
DetailsBob Reichert
ceiling inspection//danette; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa elect said was supposed to be for am tomorrow
Electrical Rough-In8/30/20058/31/20058/31/2005APART
DetailsJack Frank
wall inspection//eddie; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa walls ok
Electrical Rough-In8/30/20058/30/20058/30/2005PPART
DetailsJim Schmer
wall inspection///olga; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa conference on walls only, had smurf and bx cable inside c section of wall.
Application received  8/17/2005  
Issue permit  8/17/2005 DONE