Final | 9/28/2005 | 9/28/2005 | 9/28/2005 | A | PASS |
Bob Reichert
|
|
|
key on light fixture mandoor on garage; Phone #: ###-#### Internet Inspection Request from: Todd Holbrook ok to final
|
Electrical Rough-In | 8/19/2005 | 8/22/2005 | 8/22/2005 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 8/19/2005 at 3:51:04 PM. Contact: ###-#### corrections made, ric ok, p/s u/g n ok.
|
Rough-In Permanent Service | 8/18/2005 | 8/18/2005 | 8/18/2005 | P | FAIL |
Bob Reichert
|
|
|
tom ###-#### called contr, left corr notice, left do not cover sign, BCC address shall be posted, job id shall be posted, 312.5 abrasion protection shall be provided for gec, 300.4(D) nm cable shall be 1 1/4" from edge of framing member,110.12(A) unused openings in box shall be closed, 314.16 box fill shall not be exceeded
|
Issue permit | | | 8/18/2005 | | DONE |
|
|
|
|
Application received | | | 8/18/2005 | | |
|
|
|
|