Final | 9/2/2005 | 9/6/2005 | 9/6/2005 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer ok final correction made
|
Permanent Service | 9/6/2005 | 9/6/2005 | 9/6/2005 | P | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer p/s o/h reconnect ok correction made
|
Rough-In Permanent Service | 8/26/2005 | 8/26/2005 | 8/26/2005 | P | NH |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer still needs to remove plumbing vent from above p/s 110.26(F)(2)
|
Final | 8/22/2005 | 8/22/2005 | 8/22/2005 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dana Moyer no final cor. posted met contractor110.26(F)(2) dedicated space for p/s, 250.52(A)(1),104(A)(1) grd or bond p/s, 250.53 needs 2 grd rods, 250.148 terminate equip grds togegether and tag j box, 110.3(B) load conductors shall not be in line side or p/s, B.C.C. no violations to be retained
|
Application received | | | 8/22/2005 | | DONE |
|
|
|
This permit was created on the web by Dana Moyer
|