Second Notice ELE | 12/9/2005 | 12/9/2005 | 12/28/2005 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 11/18/2005 | 11/18/2005 | 12/9/2005 | | DONE |
Bob Reichert
|
|
|
|
Final | 11/15/2005 | 11/18/2005 | 11/18/2005 | A | PASS |
Bob Reichert
|
|
|
CORRECTIONS MADE PER NOTE, BRAD WILL BE ON-SITE, ###-####. THANK YOU; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH ok to final
|
Final | 11/2/2005 | 11/3/2005 | 11/3/2005 | P | FAIL |
Bob Reichert
|
|
|
MAJOR REMODEL; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr, left corr notice, 408.4, panel schedule needs completed, 358.30(A) emt shall be supported,230.70(B) service disc shall be marked,800.52(B)shall remove abandoned cables,and install from struct part of bldg
|
Final | 10/19/2005 | 10/20/2005 | 10/20/2005 | A | PART |
Bob Reichert
|
|
|
WE ARE READY FOR A FINAL INSPECTION SO THAT THE TENANT CAN GET OCCUPANCY FOR THE MAIN FLOOR. ANY QUESTIONS, PLEASE FEEL FREE TO CALL US. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr, left corr notice, signed t/o card, NEC 110.3 front ceiling fixtures shall be installed and lower level completed. Note: no access beyond front nw office area shall be permitted. Construction and t/o expire 11-04-05.
|
Final | 10/14/2005 | 10/17/2005 | 10/17/2005 | A | FAIL |
Bob Reichert
|
|
|
READY FOR FINAL INSPECTION FOR THE UPSTAIRS FOR OCCUPANCY. YOU CAN CONTACT THE CONTRACTOR ON HIS CELL PHONE AT ###-####. THANK YOU.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr, left correction notice, 404.9 switches shall have faceplates, 406.4 recpt shall be securely fastened,406.5 recpts shall have faceplates, 406.8(E) floor recpts shall have weatherproof covers, 314.25 boxes shall have covers, 110.12(C) there shall be no broken parts, 110.3 recpts shall be installed correctly,i.e. no hot and gnd reversed, no hots on neutrals, front recpts shalll operate, 210.8(B) gfci recpts shall be provided by sinks
|
Final | 10/7/2005 | 10/10/2005 | 10/10/2005 | A | CANC |
Bob Reichert
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa see conf
|
Conference | 10/10/2005 | 10/10/2005 | 10/10/2005 | A | DONE |
Bob Reichert
|
|
|
chris; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa met with general, they are still at least 1 week out. Told them they need to be all but done before they ask for t/o
|
Electrical Rough-In | 9/26/2005 | 9/27/2005 | 9/27/2005 | A | PASS |
Bob Reichert
|
|
|
R/I FOR COVER IN LAB AREA. BRAD IS ELECT. LH Internet Inspection Request from: BRIAN KEITH ok to cover walls only lab area
|
Electrical Rough-In | 9/13/2005 | 9/14/2005 | 9/14/2005 | P | PASS |
Bob Reichert
|
|
|
REINSPECT ROUGHIN WORK, LATE PM PLEASE. BRAD IS ON THE JOB IN AFTERNOON. THANK YOU; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH talked about clean up of exst bldg and they need to bring up to code. ric ok for walls only.
|
Electrical Rough-In | 9/2/2005 | 9/6/2005 | 9/6/2005 | A | FAIL |
Bob Reichert
|
|
|
rough in re-inspect ready. ; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corrections not made, called contr, left same corr notice, fee due
|
Electrical Rough-In | 9/1/2005 | 9/1/2005 | 9/1/2005 | P | NR |
Jack Frank
|
|
|
rough in ready for inspect this after noon, Brad Parton is on the job. Thank you; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH electrical contractor ok do not cover and correction posted for low voltage contractor to bld05-01608
|
Electrical Rough-In | 8/24/2005 | 8/25/2005 | 8/25/2005 | A | NH |
Bob Reichert
|
|
|
electric rough in. thank you; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called and said to re-schedule
|
Application received | | | 8/24/2005 | | DONE |
|
|
|
This permit was created on the web by BRIAN KEITH
|