Permanent Service | 9/20/2005 | 9/21/2005 | 9/21/2005 | A | PASS |
William E Thomas
|
|
|
Re inspection for corrections as per Pat Lass.; Phone #: ###-#### Internet Inspection Request from: Rich Rice p/s o/h r ok
|
Final | 9/21/2005 | 9/21/2005 | 9/21/2005 | A | PASS |
William E Thomas
|
|
|
|
Permanent Service | 9/19/2005 | 9/19/2005 | 9/19/2005 | P | FAIL |
Pat Lass
|
|
|
meter base/ main disconnect only due to damage from tree falling on IPCO triplex and destroying original meter/main.; Phone #: ###-#### Internet Inspection Request from: Rich Rice broken ground clamp in basement inproper and loose grounding clamps cover won't open 90deg. mast to support only service conductors mast not supported within 30 in. of weatherhead ground rod is over 1 ft above ground.
|
Application received | | | 9/19/2005 | | DONE |
|
|
|
This permit was created on the web by Rich Rice
|