Temporary Service | 9/22/2005 | 9/22/2005 | 9/22/2005 | P | PASS |
Jack Frank
|
|
|
set new temp pole; Phone #: ###-#### Internet Inspection Request from: Todd Holbrook t/s o/h new ok
|
Temporary Service | 9/21/2005 | 9/21/2005 | 9/21/2005 | P | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/21/2005 at 8:17:50 AM. Contact: ###-####. cor. posted called 312.5 needs conn for GEC,406.8 inuse covers, 110.3(B) use manufactures breakers only, 590.6(B)(1) gfci for all 240 V recepts, 110.3 (A) secure all boxes nipples, lock nuts fee due posted
|
Temporary Service | 9/20/2005 | 9/21/2005 | 9/21/2005 | A | NR |
Jack Frank
|
|
|
###-#### no t/s at site
|
Temporary Service | 9/19/2005 | 9/19/2005 | 9/19/2005 | P | NR |
Jack Frank
|
|
|
tom ###-#### -for t/p called no t/s at site
|
Application received | | | 9/19/2005 | | |
|
|
|
|
Issue & PRINT permit | | | 9/19/2005 | | DONE |
|
|
|
|