Final | 11/10/2005 | 11/14/2005 | 11/14/2005 | A | PASS |
Jack Frank
|
|
|
###-####--gayle--call 1st before insp for homeowner ok card signed
|
Final | 11/10/2005 | 11/10/2005 | 11/10/2005 | P | FAIL |
Jack Frank
|
|
|
gayle; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa not ready no power to shop reinspection fee
|
Stop Work/Reinspection Fee | 11/10/2005 | 11/10/2005 | 11/10/2005 | P | DONE |
Jack Frank
|
|
|
gayle; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa reinspection fee due been out there too many times , posted corrections , or not ready, and all corrections not made called for final not ready because he does not have power to shop could not inspect
|
Final | 11/9/2005 | 11/9/2005 | 11/9/2005 | P | PART |
Jack Frank
|
|
|
gayle; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa r/i ok corrections made, still needs to terminate GEC to equip grd bus 250.32(B)(1)
|
Final | 11/7/2005 | 11/7/2005 | 11/7/2005 | P | FAIL |
Jack Frank
|
|
|
gail ###-#### cell cor. met owner 250.32(B)(1) isolate grds and neuts at shop service 300.4 nail plates and 11/4" 314.16 box fill, 210.70 needs outside for exit door, 314.17 conn for bell box, remove devices from boxes so I can inspect
|
Electrical Rough-In | 9/26/2005 | 9/27/2005 | 9/27/2005 | A | PASS |
Jack Frank
|
|
|
underground trench inspection ///gayle; Phone #: ###-#### Internet Inspection Request from: Barbara electrode ok for dirt cover
|
Electrical Rough-In | 9/23/2005 | 9/26/2005 | 9/26/2005 | A | PART |
Jack Frank
|
|
|
trench inspection//gayle; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa electrode for concrete, and u/g
|
Electrical Rough-In | 9/23/2005 | 9/23/2005 | 9/23/2005 | P | FAIL |
Jack Frank
|
|
|
trench inspection//gayle; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa conference ok only owner needs concrete encased electrode at new shop, and u/g, has over 360 degrees of bends, and shall be 18" below grade where not under concrete
|
Application received | | | 9/23/2005 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 9/23/2005 | | DONE |
|
|
|
|