Final | 6/8/2006 | 6/9/2006 | 6/8/2006 | P | PASS |
Jack Frank
|
|
|
Nickoli; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt final ok correction made by electrical contr. permit ele06-02117
|
Final | 6/8/2006 | 6/8/2006 | 6/8/2006 | P | CANC |
Jack Frank
|
|
|
alex - call prior to insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley - homeowner canceled 12:01 p.m.
|
Final | 6/6/2006 | 6/6/2006 | 6/6/2006 | P | FAIL |
Jack Frank
|
|
|
nickoly; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr. met owner not all corrections made and new ones created, 300.14 6 ' free conductor, upstairs hall left of stairs, 110.14(B) needs splicing device grds at garage fixtures, 314.16& 43, upstairs bed rm top of stairs left, and hall box fill and screws inplastic box, 110.3(A&B) replace boxes in M bed rm and den where holes are drilled and boxes are damaged
|
Final | 5/30/2006 | 5/30/2006 | 5/30/2006 | P | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung corr. met owner, 110.14 clockwise wire at screw terminals, 200.11 reversed polarity MB plugs,also needs outlet left of bathrm door over 6ft 210.52(A), 406.3 open grd recepts upstairs bedrm, also no power upstairs hallways314.20 box extensions in paneled walls den, 314.3 shall use non metallic sealtight at W H408.4 panel schedule shall be specific as to location and purpose of circuits 410.14 acess hole required in back of flourescence fixtures garage, 406.4 recepts loose mounting all locations, gfci in kit bad or wiring messed up, shall check all wiring before inspection requested for final too many things wrong
|
Final | 10/17/2005 | 10/17/2005 | 10/17/2005 | P | CANC |
William E Thomas
|
|
|
alex --call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
|
Rough-In Permanent Service | 10/17/2005 | 10/17/2005 | 10/17/2005 | P | PASS |
William E Thomas
|
|
|
alex --call 1st before insp ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ri ok p/s u/g n ok
|
Electrical Rough-In | 10/11/2005 | 10/11/2005 | 10/11/2005 | P | FAIL |
Jack Frank
|
|
|
nickoly; Phone #: ###-#### Internet Inspection Request from: Barbara Moore cor. do not cover called300.4(A)(1)&(D), 300.14 equip grds, 314.16, 210.52(A), 314.43, 314.20 , needs prints, complete all wiring and makeup if more violations created permit could be voided,, COW
|
Conference | 9/29/2005 | 9/29/2005 | 9/29/2005 | P | DONE |
Jack Frank
|
|
|
alex-- ###-#### cell --call 1st before insp please ok
|
Change Status to I | | | 9/29/2005 | | DONE |
|
|
|
changed status to issued --customer came back to get permit
|
(F) Reprint permit | | | 9/29/2005 | | DONE |
|
|
|
|
Application received | | | 9/28/2005 | | |
|
|
|
|
VOIDED CHANGE STATUS | | | 9/28/2005 | | DONE |
|
|
|
per jim schmer homeowner cannot apply for permit unless he is living in the house/voided permit /9-28-05/mls
|