Final | 2/12/2006 | 2/13/2006 | 2/13/2006 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 2/12/2006 at 11:40:01 AM. Contact: ###-####. ok
|
Final | 2/7/2006 | 2/7/2006 | 2/7/2006 | P | FAIL |
Jack Frank
|
|
|
Brandon; Phone #: ###-#### Internet Inspection Request from: Elizabeth Esong cor. called 210.11(C)(3) pantry outlet shall not be on bath circuit, no power to recept below window in kit (counter) secure outside cover so they don't fall off when testing recept
|
Permanent Service | 10/21/2005 | 10/21/2005 | 10/21/2005 | P | PASS |
Mike Kinnear
|
|
|
brandon; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa p/s o/h n ok corrections made
|
Permanent Service | 10/18/2005 | 10/18/2005 | 10/18/2005 | P | FAIL |
Jack Frank
|
|
|
write corrections to change to single meter and make sub panels meet code cor. posted only 1 meter and all wiring shall meet current NEC called
|
Permanent Service | 10/11/2005 | 10/12/2005 | 10/12/2005 | A | PASS |
Jack Frank
|
|
|
brandon ###-#### p/s o/h new ok
|
Permanent Service | 9/30/2005 | 10/3/2005 | 10/3/2005 | A | NR |
Jack Frank
|
|
|
brandon ###-####
|
Electrical Rough-In | 9/30/2005 | 10/3/2005 | 10/3/2005 | A | PART |
Jack Frank
|
|
|
upher ground inspection///brandon ###-#### electrode ok for concrete cover
|
Application received | | | 9/30/2005 | | |
|
|
|
|
Issue permit | | | 9/30/2005 | | DONE |
|
|
|
|