Temporary Service | 10/7/2005 | 10/7/2005 | 10/7/2005 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas corrections made, t/s u/g n ok
|
Temporary Service | 10/6/2005 | 10/6/2005 | 10/6/2005 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas called contr, left corr notice, 250.64(C) grounding electrode conductor shall be installed in one continuous length without a splice or joint.
|
Temporary Service | 10/5/2005 | 10/5/2005 | 10/5/2005 | P | FAIL |
Bob Reichert
|
|
|
heath; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections not made
|
Temporary Service | 10/4/2005 | 10/4/2005 | 10/4/2005 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Joe Thomas called contr, left message, left correction notice, fee due for re-inspection, 250.52(A)(5) rod electrodes shall be not less than 8' in length, 250.56 single electrode shall be augmented by one additional electrode, 312.5 conductors entering enclosures shall be protected from abrasion
|
Application received | | | 9/30/2005 | | DONE |
|
|
|
This permit was created on the web by Joe Thomas
|