Temporary Service | 10/6/2005 | 10/7/2005 | 10/7/2005 | A | PASS |
Mike Kinnear
|
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore t/s u/g n ok
|
Temporary Service | 10/6/2005 | 10/6/2005 | 10/6/2005 | P | FAIL |
Bob Reichert
|
|
|
jim ###-#### called contr, left corr notice, fee due, 110.12(C) there shall be no broken parts, recpts, 312.5 conductors entering enclosure shall be protected from abrasion, 250.53(G) rod electrode shall be at least 8' long and driven to 8' depyh
|
Issue permit | | | 10/6/2005 | | DONE |
|
|
|
|
Application received | | | 10/6/2005 | | |
|
|
|
|