Third Notice | | 1/12/2006 | 2/28/2006 | | DONE |
|
|
|
|
Third Notice ELE | 1/12/2006 | 1/12/2006 | 2/21/2006 | | DONE |
|
|
|
Second Notice has not been responded to.
|
Second Notice ELE | 12/28/2005 | 12/28/2005 | 1/12/2006 | | DONE |
|
|
|
First Notice has not been responded to.
|
First Notice | 11/29/2005 | 11/29/2005 | 12/28/2005 | | DONE |
Bob Reichert
|
|
|
|
Final | 11/29/2005 | 11/29/2005 | 11/29/2005 | P | PASS |
Bob Reichert
|
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ok to final, no card to sign on job
|
Electrical Rough-In | 10/11/2005 | 10/12/2005 | 10/12/2005 | A | PART |
Pat Lass
|
|
|
dan; Phone #: ###-#### Internet Inspection Request from: Barbara Moore new walls only. this does not include the ceiling or bathroom wall.
|
Electrical Rough-In | 10/7/2005 | 10/7/2005 | 10/7/2005 | P | FAIL |
Bob Reichert
|
|
|
dan ###-#### called contr, left corr notice,300.4(D) mc cable shall be 1 1/4" from edge of framing member,358.30(A) emt shall be strapped within 3' of box, 312.5 conductors entering enclosures shall be protected from abrasion, 348.30 flex shall be supported within 12" of box, 210.8(B) bath recpt shall be gfci , 300.11(A) raceways shall not be supported by ceiling grids, BCC no violations shall be retained
|
Issue & PRINT permit | | | 10/7/2005 | | DONE |
|
|
|
|
(F) Reprint permit | | | 10/7/2005 | | DONE |
|
|
|
|
Application received | | | 10/7/2005 | | |
|
|
|
|