Final | 5/10/2006 | 5/10/2006 | 5/10/2006 | P | PASS |
Bob Reichert
|
|
|
robert --call 1st for access ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called owner, left survey,nec 352(A) rnc shall be strapped within 3' of box or fitting, 408.4 circuit directory shall be clear concise and distinguished from other circuits, ok to final
|
Electrical Rough-In | 10/19/2005 | 10/19/2005 | 10/19/2005 | P | PASS |
Bob Reichert
|
|
|
robert; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corr made, ric ok
|
Conference | 10/14/2005 | 10/17/2005 | 10/17/2005 | A | CANC |
Bob Reichert
|
|
|
please call 30 min prior to meet you///bob; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa see ri
|
Electrical Rough-In | 10/17/2005 | 10/17/2005 | 10/17/2005 | A | FAIL |
Bob Reichert
|
|
|
please call 30 min prior to meet you///bob; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called owner, did conference and r/i since he did over weekend anyway. left corr notice, 312.5 conductors entering enclosure shall have abrasion protection,200.6(B) id shall be provided for grounded conductor, 250.110 metal boxes shall be grounded, 334.30 nm cable shall be stapled within 12 " of box, BCC all make-up shall be done, u/g shall be inspected before cover.
|
Application received | | | 10/13/2005 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 10/13/2005 | | DONE |
|
|
|
|