Final | 10/25/2005 | 10/25/2005 | 10/25/2005 | P | PASS |
Mike Kinnear
|
|
|
joel; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok final
|
Permanent Service | 10/24/2005 | 10/25/2005 | 10/25/2005 | A | FAIL |
Mike Kinnear
|
|
|
JOEL//please call 30 min prior; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ground wire from water pipe has to go to main service. bond hot & cold water pipes
|
Permanent Service | 10/25/2005 | 10/25/2005 | 10/25/2005 | P | PASS |
Mike Kinnear
|
|
|
joel; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles p/s o/h reconnect ok
|
Change Status to I | | | 10/24/2005 | | |
|
|
|
per Jim Schmer ok to reopen 10/24/05 LEG
|
Final | 10/20/2005 | 10/20/2005 | 10/20/2005 | P | FAIL |
Mike Kinnear
|
|
|
joel; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles t/w owner he needs an electrical contractor to do service. sub panal so messed up it needs to be replaced. (note almost all the bottom of panal cut out. grounds & neut. not sperated) can not run 4 wires for service connection, needs to be 3 wires sun light resistant type. grounding not done correct (needs #6cu wire to ground rods) need to connect water system for grounding electrode.
|
VOIDED CHANGE STATUS | | | 10/20/2005 | | DONE |
|
|
|
Per Mike Kinnear void permit, homeowner cannot do wiring needs to hire contractor to do job, if any questions call Mike K.///10/20/05 LEG
|
Application received | | | 10/18/2005 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 10/18/2005 | | DONE |
|
|
|
|