Final | 7/31/2006 | 7/31/2006 | 7/31/2006 | P | PASS |
Jack Frank
|
|
|
Internet Inspection Request from: Bob Glenn ok builder will move fence for clearence for panel
|
Final | 6/1/2006 | 6/1/2006 | 6/1/2006 | P | CANC |
Jack Frank
|
|
|
BILL; Phone #: ###-#### Internet Inspection Request from: Bob Glenn Inspection cancelled from web by: Bob Glenn
|
Rough-In Permanent Service | 4/7/2006 | 4/7/2006 | 4/7/2006 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Bob Glenn r/i ok p/s o/h new ok
|
Rough-In Permanent Service | 3/31/2006 | 4/4/2006 | 4/4/2006 | A | FAIL |
Jack Frank
|
|
|
###-#### Internet Inspection Request from: Bob Glenn corr. called 300.4 nail plates and 11/4" 225.31,36 needs main disconnect at house service, 210.52(C)(1) counter outlet spcing right and left of sink, 314,17 (A&C) replace 2,3,4 gang boxes with broken clamps, 334.30 shall not staple romex on edge 314.43 no nails allowed in plastic boxes outside boxes called left message
|
Change Status to I | | | 3/31/2006 | | DONE |
|
|
|
final inspection not done yet
|
Temporary Service | 11/16/2005 | 11/16/2005 | 11/16/2005 | P | PASS |
Jack Frank
|
|
|
OVERHEAD TEMP POLE. IN ALLEY OFF IRVING BETWEEN GARDEN AND WILSON. QUESTIONS OR CONCERNS CALL BILL AT ###-####. THANKS. Internet Inspection Request from: Bob Glenn t/s o/h new ok
|
Electrical Rough-In | 10/21/2005 | 10/21/2005 | 10/21/2005 | P | PART |
Jack Frank
|
|
|
###-#### - bob Note: underground ok
|
Issue & PRINT permit | | | 10/21/2005 | | |
|
|
|
|
Application received | | | 10/21/2005 | | |
|
|
|
|