Information based on query as of Saturday, August 17, 2024.
Permit Information
Permit NumberELE05-03858
StatusFinaled
Name STEPHEN'S ELECTRIC INC
Site Address 11092 W GREYLING DR
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/20/20062/21/20062/21/2006APASS
DetailsJack Frank
Scheduled by a contractor via Hello! on 2/20/2006 at 9:47:33 AM. Contact: ###-####. ok
Permanent Service11/1/200511/2/200511/2/2005APASS
DetailsJack Frank
Scheduled by a contractor via Hello! on 11/1/2005 at 1:29:33 PM. Contact: ###-####. p/s u/g new ok
Rough-In Permanent Service10/27/200510/28/200510/28/2005PPART
DetailsJack Frank
Scheduled by a contractor via Hello! on 10/27/2005 at 2:47:43 PM. Contact: ###-####. r/i only ok see added fee due inspection for p/s
Stop Work/Reinspection Fee10/28/200510/28/200510/28/2005PFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 10/27/2005 at 2:47:43 PM. Contact: ###-####. fee due and cor. posted for p/s correction not made,250.64(C) GEC shall be continuous shall not splice in panel
Rough-In Permanent Service10/21/200510/27/200510/27/2005PFAIL
DetailsJack Frank
steve-- ###-#### cor ,do not cover called let message, 250.64 (C)&(E) shall not splice GEC, and use conn. for GEC at panels,314.43 no nails or screws in plastic boxes,210.52(B) remove range hood from kit circuit, complete all makeup outside boxes
Application received  10/21/2005  
Issue & PRINT permit  10/21/2005